Specification Number:VLF-500
Product Introduction
 The VESDA VLF-500 detector is a very early warning smoke  detector designed to protect small, business-critical environments of less  than 500 m2 (5,380 sq. ft.).
 The detector works by continually drawing air into sampling holes in a pipe network. The air is filtered and passed into a detection chamber where light scattering technology detects the presence of very small amounts 
of smoke. Detector status information is communicated on the detector display and via relays or optional interface cards.
 Out-of-the-Box Operation
 The VLF can be installed and commissioned out-of-the-box without the need for a special interface or software programming tools.
 In operation, the unique Smoke DialTM display provides the user with an instant understanding of a smoke event, even from a distance. Should a fault occur, the user simply opens the field service door and activates the Instant Fault Finder feature to determine the specific fault condition. This information can then be passed onto their fire service company, ensuring that service technicians arrive onsite fully prepared.
 Ultrasonic Flow Sensing
 The patented Ultrasonic Flow Sensing used in the VLF provides a direct reading of the sampling pipe flow rate. The system is immune to air temperature and pressure changes and is unaffected by contamination. The VLF is the first air sampling smoke detector to use ultrasonic flow sensing.

Features
 • Out-of-the-Box Installation and Commissioning
 • Ultrasonic Airflow Sensing
 • Laser-Based Absolute Smoke Detection
 • Pre-engineered pipe network designs 
• Programmable Alarm Thresholds
 • Clean air barrier optics protection
 • Instant Recognition Display
 • Instant Fault Finder™
 • AutoLearn™ Smoke
 • AutoLearn™ Flow
 • Field Service Access Door
 • Multiple Event Logging in separate logs
 • Event log – up to 18000 events
 • Offline/online configuration capability
 • Up to 500 m2 (5,380 sq. ft.) coverage

 Listings / Approvals
 • CCC 
• FM Class I Div II 
• ActiveFire (ISO/AS 7240-20)
 • CE
 • UKCA
 • LPCB
 • VdS
 • NF
 • EN 54-20
Class A (30 holes / 0.05% obs/m)--
 Class B (30 holes / 0.15% obs/m)
 Class C (30 holes / 0.32% obs/m)
 Classification of any configuration is determined using ASPIRE.
 Regional approvals listings and regulatory compliance vary between product models. Refer to www.xtralis.com for the latest product approvals matrix.


 Specifications
 Input Power Voltage: 24V DC Nominal (18-30 V DC)
 410 mA nominal, 490 mA in alarm
 Dimensions (W x H x D) 256 mm x 183 mm x 92 mm (101/16 in x 71/5 in x 32/3 in)
 Weight Approx. 2 kg (4.4 lbs)
 IP Rating IP30
 Mounting Upright, inverted or horizontal
 Operating Conditions*
 Ambient: 0°C to 38°C (32°F to 100°F)
 Sampled Air: -20°C to 60°C (-4°F to 140°F) *
 Humidity: 5% to 95% RH, non-condensing
 * Sampled Air temperature shall reach Ambient Detector temperature 
upon entry into Detector. Refer to Xtralis Design Guides & Application 
Notes for sampled air pre-conditioning.
 Sampling Network
 • Maximum pipe lengths: 1 x 50 m (150 ft) (Max. 24 holes) 
2 x 30 m (90 ft) per branch (Max. 12 holes per branch)
 • Sampling Hole Options: Pre-Engineered Option or 
Maximum Pipe length in accordance with Pipe Modelling 
Design Tool (ASPIRE™)
 Air Inlet Pipe Accepts both metric and American standard pipe sizes  
Metric: 25 mm (1.05 in.)  American Pipe: IPS 21 mm (¾ in.)
 Area Coverage Up to 500 m2 (5,380 sq. ft.) depending on local codes and 
standards
 Relay Outputs 3 changeover relays (Fire 1, Action, Fault), Contacts rated 2A 
@ 30 VDC (max). NO/NC Contacts
 Cable Access 3 x 25 mm (11/16
 in.) cable entries (1 rear entry, 2 top entry)
 Cable Termination Screw Terminals 0.2-2.5 mm2 (30-12 AWG)
 Interfaces
 Shown in Terminal Block Connections diagram, to right, plus an RS232 Programming Port. General Purpose Input (GPI) 
interface offers: Reset, Disable, Standby, Alarm set 1, Alarm set 
2 and External Input functions.
 Alarm Threshold Setting Range
 Alert, Action: 0.025 - 2.00% obs/m (0.008 - 0.614% obs/ft)
 Fire 1, Fire 2: 0.025 - 20.00% obs/m (0.008 - 6.575% obs/ft)
 Individual Alarm Delays: 0 – 60 seconds 
Two Alarm Threshold Settings: Either time or GPI based
 Display
 • 4 Alarm State Indicators
 • Smoke Level Indicator
 • Reset, Disable and Test Control
 • Fault and Disabled Indicators
 • Instant Fault Finder
 • Smoke and Flow AutoLearn Controlss
 Event Log
 Up to 18000 events, time and date stamped in separate, nonvolatile, logs for:
 Smoke Level, Flow Level, Detector Status and Faults
 AutoLearn Smoke & Flow
 • Automatically set acceptable alarm thresholds for both smoke and flow levels
 • Minimum 15 minutes, maximum 15 days (default 14 days)
 • During AutoLearn thresholds are NOT changed from pre-set values

 Ordering Information
 
 Ordering Code   
Description
Ordering Code
Description
VLF-500-00 
VESDA VLF. European language set. English display labels
VIC-010
 VESDAnet Interface Card
 VLF-500-01
 VESDA VLF. European language set. International display labels
VIC-020 
Multifunction Control Card (MCC)
VLF-500-02 
VESDA VLF. English + Asian 
language set. International 
display labels
VIC-030 
Multifunction Control Card 
(MCC) with Monitored 
Powered Output (MPO)
VLF-500-03 
VESDA VLF. Scandinavian 
language set. International 
display labels
VIC-005 
Filter Cartridge
VLF-500-04 
VESDA VLF. English + Russian 
language set. International 
display labels
VIC-715
 Aspirator for VESDA VLF-500
VLF-500-05
VESDA VLF. English + Eastern Euro language set. International display labels